Toshiba T2N User Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 272
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
Features
-
xv
-
nEnhanced communication
The T2N has RS-232C/RS485 serial communication port. Either interface can be selected.
Using this port, one of the following communication functions can be used.
lComputer link mode :Connection with higher level computer, MMI/SCADA system,
modem, etc.
lData link mode :Easy data linkage between two T2Ns or T2E .
lFree ASCII mode :Active communication between serial ASCII devices. (bar code
readers, etc.).
nProgrammer port function
The T2Ns RS-232C programmer port supports the T-series computer link protocol. This
results in easy connection to a higher level computer, an operator interface unit, a modem,
etc.
n High speed processing
The T2N excels at applications where high speed processing is required.
0.33µs/contact 0.44µs/coil
1.2µs/16-bit transfer 1.63µs/16-bit addition
n Advanced instruction set
The T2N offers 24 basic relay-ladder instructions and 192 function block instructions,
including the following.
Arithmetic operation Data manipulations Trigonometric functions
PID/ramp/integral Subroutine call For-Next loop
Averaging/filtering ASCIIHex conversion Floating-point math
n Two programming Languages
The T2N supports two programming languages: Ladder Diagram (LD) and Sequential
Function Chart (SFC). By selecting the appropriate language, or combination of the two,
program development time can be greatly reduced.
n Sufficient capacity
The T2N has 24K steps program memory and controls up to 2,048 I/O points.