2. User Program Configuration
140 PROSEC T2N
(8) Retentive memory area Designation
This sets and registers the address limits for the auxiliary register
(RW), timer register(T), counter register(C) and data register(D)
which retain pre-power cut data out of the user data when there is
a power cut/power restoration. The limits registered here are
outside the subjects of the user initialization process. For each of
these registers, the limits from the leading address(0) to the
designated address are the retentive memory areas. The power
cut retention limit designations can be registered /monitored on
the system information screen of the programmer.
(9) 10ms Timer Range Setting
This is invalid (setting is not needed.) in the T2N.
(10) Start Mode
This is invalid (setting is not needed.) in the T2N.
(11) Scan Time Setting
This sets and registerd the scan mode (floating/constant). When
no scan time is registered (blank), the mode becomes the floating
scan mode. When a numerical value is set for the scan time, the
mode becomes a constant scan mode which takes that time as
the scan cycle. The setting for the scan cycle is 10-200ms (in
10ms units). The scan time setting can be registered/monitored
on the system information screen of the programmer.
(12) Sub-Program Execution Time
This is invalid (setting is not needed.) in the T2N.
(13) Fixed cycle Timer Interrupt Interval
This sets and registers the interrupt cycle of the time interrupt
program. The setting limits are 5-1000ms (in 5ms units). The
fixed timer interrupt cycle can be registered /monitored on the
system information screen of the programmer.