Toshiba Tosvert VF-AS1 User Manual Page 232

  • Download
  • Add to my manuals
  • Print
  • Page
    / 312
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 231
E6581300
J-2
10
Selection of wiring equipment
No-fuse breaker (MCCB)
Magnetic contactor
(MC)
Input current[A]
Without Reactor With Reactor
Without
Reactor
With
Reactor
Voltage
class
Applicable
motor [kW]
Inverter model
Without
Reactor
With
Reactor
Rated
current
[A]
Type
form
(*1)
Rated
current
[A]
Type
form
(*1)
Type
form
(*1)
Type
form
(*1)
0.4 VFAS1-2004PL 3.5 2.1 6.3 GV2 L10 4 GV2 L08 LC1D096 LC1D096
0.75 VFAS1-2007PL 6.1 3.2 10 GV2 L14 6.3 GV2 L10 LC1D096 LC1D096
1.5 VFAS1-2015PL 11.5 6.4 18 GV2 L20 10 GV2 L14 LC1D096 LC1D096
2.2 VFAS1-2022PL 15 9.3 25 GV2 L22 14 GV2 L16 LC1D096 LC1D096
3.7/4.0 VFAS1-2037PL 26.0 15.5 32 GV2 L32 25 GV2 L22 LC1D126 LC1D096
5.5 VFAS1-2055PL 35 22. 5 50 NJ50EB 32 GV2 L32 LC1D126 LC1D126
7.5 VFAS1-2075PL 45 34.5 60 NJ100FB 40 NJ50EB LC1D326 LC1D256
11 VFAS1-2110PM - 53.5 - - 75 NJ100FB - LC1D506
15 VFAS1-2150PM - 72 - - 100 NJ100FB - LC1D506
18.5 VFAS1-2185PM - 77 - - 100 NJ100FB - LC1D506
22 VFAS1-2220PM - 88 - - 125 NJ225FB - LC1D806
30 VFAS1-2300PM - 125 - - 150 NJ225FB - LC1D806
37 VFAS1-2370PM - 140 - - 175 NJ225FB - LC1D115J
45 VFAS1-2450PM - 165 - - 200 NJ225FB - LC1D150J
55 VFAS1-2550P - 200 - - 250 NJ400F - LC1F185J
200V
class
75 VFAS1-2750P - 270 - - 350 NJ400F - LC1F265J
0.75 VFAS1-4007PL 3.7 2.1 5 GV2 L10 4 GV2 L08 LC1D096 LC1D096
1.5 VFAS1-4015PL 5.8 3.8 10 GV2 L14 6.3 GV2 L10 LC1D096 LC1D096
2.2 VFAS1-4022PL 8.2 5.7 14 GV2 L16 10 GV2 L14 LC1D096 LC1D096
3.7/4.0 VFAS1-4037PL 14.0 8.7 18 GV2 L20 14 GV2 L16 LC1D096 LC1D096
5.5 VFAS1-4055PL 20.5 12.7 32 GV2 L32 25 GV2 L22 LC1D126 LC1D126
7.5 VFAS1-4075PL 27 16.3 32 GV2 L32 25 GV2 L22 LC1D186 LC1D186
11 VFAS1-4110PL 36.5 21.5 50 NJ50EB 30 NJ30E LC1D256 LC1D186
15 VFAS1-4150PL 48 33.5 60 NJ100FB 40 NJ50EB LC1D326 LC1D256
18.5 VFAS1-4185PL - 45.5 - - 60 NJ100FB - LC1D326
22 VFAS1-4220PL - 50 - - 60 NJ100FB - LC1D326
30 VFAS1-4300PL - 66 - - 100 NJ100FB - LC1D506
37 VFAS1-4370PL - 84 - - 100 NJ100FB - LC1D806
45 VFAS1-4450PL - 105 - - 125 NJ225FB - LC1D806
55 VFAS1-4550PL - 120 - - 150 NJ225FB - LC1D806
75 VFAS1-4750PL - 165 - - 200 NJ225FB - LC1D115J
90 VFAS1-4900PC - 170 - - 200 NJ225FB - LC1D150J
110 VFAS1-4110KPC - 200 - - 250 NJ400F - LC1D185J
132 VFAS1-4132KPC - 240 - - 300 NJ400F - LC1D225J
160 VFAS1-4160KPC - 290 - - 350 NJ400F - LC1D265J
200 VFAS1-4200KPC - 360 - - 500 NJ600F - LC1D400J
220 VFAS1-4220KPC - 395 - - 500 NJ600F - LC1D400J
280 VFAS1-4280KPC - 495 - - 600 NJ600F - LC1D500J
355 VFAS1-4355KPC
400 VFAS1-4400KPC
400V
class
500 VFAS1-4500KPC
(*1): Type forms of Toshiba Schneider Electric Ltd. products.
(*2): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
(*3): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*4): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current for
the motor rated current.
(*5): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*6): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability of