Toshiba VF-nC1 User Manual Page 56

  • Download
  • Add to my manuals
  • Print
  • Page
    / 143
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 55
E6581090
E-4
5
5.3 Standard default setting
V[R
: Standard setting mode selection
Title FunctionAdjustment rangeDefault setting
V[R
Standard setting
mode selection
0 : -
1 : Default setting 50Hz
2 : Default setting 60Hz
3 : Default setting
4 : Trip clear
5 : Cumulative operation time clear
0
This function will be displayed as 0 during reading on the right. This previous setting is
displayed on the left.
Ex. 3  0
V[R cannot be set during the inverter operating. Always stop the inverter first and then program.
[Setting values]
 50Hz standard setting (V[R=)
To se t the following parameters for a base frequency of 50Hz, set the V[R parameter to 1.
(This setting does not affect the settings of any other parameters.)
Maximum frequency HJ
: 50Hz
Base frequency 1 XN
: 50Hz
Base frequency 2 H
: 50Hz
Upper limit frequency WN
: 50Hz
VI/S3 point 2 frequency H
: 50Hz
Motor rated speed H
: 1410min
-1
 60Hz standard setting (V[R=)
To se t the following parameters for a base frequency of 60Hz, set the V[R parameter to 2.
(This setting does not affect the settings of any other parameters.)
Maximum frequency HJ
: 60Hz
Base frequency 1 XN
: 60Hz
Base frequency 2 H
: 60Hz
Upper limit frequency WN
: 60Hz
VI/S3 point 2 frequency H
: 60Hz
Motor rated speed H
: 1710min
-1
 Default setting (V[R=)
Setting V[R to will return all parameters to the standard values that were programmed at the
factory.
When 3 is programmed, < KPKV will be displayed for a short time after setting and will then
be erased and displayed the original indicationPQ(Setup parameter). (Only for VFNC1 (S)-
□□□□P-W type) This setting clears all trip history data but it does not clear cumulative
operation time data. This setting does not affect the settings of the following parameters.
FM/OUT terminal functions selection HOUN Meter adjustment HO
Analog input/logic input function selection H Sink/source selection H
Free notes H
See 4.1.1 for setting of setup parameters.
 Trip clear (V[R=)
Setting V[R to initializes the past four sets of recorded error history data.
*(The parameter does not change.)
 Cumulative operation time clear (V[R=)
Setting V[R to allows the initial resetting of the cumulative operation time monitor (0 [zero]
time).
*(The parameter does not change.)
Function
Allows setting of all parameters to the standard default setting, etc. at one time. (Except
the setting of HO)
Page view 55
1 2 ... 51 52 53 54 55 56 57 58 59 60 61 ... 142 143

Comments to this Manuals

No comments