TOSVERT VF-nC1 Instruction ManualIndustrial InverterTOSHIBA INTERNATIONAL CORPORATION13131 West Little York RD., Houston, TX 77041, U.S.ATEL: +1-713-
E6581090A-11Rated output currentand capacityPower supplyInverter typeApplicablemotor labelWarning labelPower supplyMotor capacityPet nameApplicablemot
E6581090H-388.2 Display of trip informationIf the inverter trips, an error code is displayed to suggest the cause. In the status monitor mode, allt
E6581090H-48 Example of call-up of trip informationItemdisplayedKeyoperatedLEDdisplayCommunicationNo.DescriptionQRStatus monitor mode (The code blink
E6581090H-58(Continued)ItemdisplayedKeyoperatedLEDdisplayCommunicationNo.DescriptionCPU1versionX FE08 The version of the CPU1 is displayed.CPU2vers
E6581090I-199. Taking measures to satisfy the CE / UL / CSA9.1 Compliance with CE Marking9.1.1 AbstractIn Europe, EMC directive is enforced
E6581090I-299.1.3 Compliance with EMC directive9.1.3.1 The model, noise filter inside(1) Single-phase 200V class : VFNC1S-2002PL to 2022P
E6581090I-399.1.3.2 The models without EMI filters(1) Shingle-phase 100V class : VFNC1-1001P to 1007PThree-phase 200V class : VFNC1-2001P to 2022PShin
E6581090I-49(6) Installation of the zero-phase and/or the ferrite core can also effectively reduce the radiatednoise further. (Input or/and output of
E6581090I-59【Accessories for countermeasure】- Shielded cable : Showa electric Wire & Cable Co. LTD.Type form/ CV-S, 600V or less- Shielded cable :
E6581090I-699.1.5 Compliance with Low voltage directivePlease carry out the below mentioned countermeasures for the Low Voltage Directiv
E6581090I-79Tab le 4. AIC and fuseVoltage classCapacity ofapplicable motor(kW)Inverter modelAIC(Interruptingcapacity)Fuse class andcurrents(A)0.1 VFN
E6581090A-211.3 Name and function of each part1.3.1 Operation keypad panelRUN keyPressing this key whilethe RUN key lamp islighted starts
E6581090J-11010. Peripheral devices DangerMandatory• When using wiring materials and their optional devices for the inverter, they mustbe installed i
E6581090J-210 Selection of wiring devicesNon-fuse circuit breaker (MCCB)Earth leakage break er (ELCB)Magnetic contactor(MC)Overload relay(THR)Witho
E6581090J-31010.2 Installation of a magnetic contactorIf using the inverter without installing a magnetic contactor (MC) in the primary circuit, use a
E6581090K-11111. Table of parameters and data11.1 User parametersTitle Function UnitMinimum settingunit Panel/CommunicationAdjustment rangeDefaultsett
E6581090K-211TitleCommunicationNo.Function UnitMinimum settingunit Panel/CommunicationAdjustment rangeDefaultsettingUsersettingReferenceV[R 0007 Stand
E6581090K-31111.3 Extended parameters • Input/output parametersTitleCommunicationNo.Function UnitMinimum settingunit Panel/CommunicationAdjustment ran
E6581090K-411 • Frequency parametersTitleCommunicationNo.Function UnitMinimum settingunit Panel/CommunicationAdjustment rangeDefaultsettingUsersetting
E6581090K-511 • Operation mode parametersTitleCommunicationNo.Function UnitMinimum setting unitPanel/CommunicationAdjustment rangeDefaultsettingUserse
E6581090K-611 • Acceleration/deceleration time parametersTitleCommunicationNo.Function UnitMinimum settingunit Panel/CommunicationAdjustment rangeDefa
E6581090K-711 • Operation panel parametersTitleCommunicationNo.Function UnitMinimum settingunit Panel/CommunicationAdjustment rangeDefaultsettingUsers
E6581090A-31[Front panel]Front coverCharge lampIndicates that high voltage is stillpresent within the inverter. Do notopen the terminal board cover wh
E6581090K-811 Default settings by inverter ratingTor q ue b o o s t M otor ratedcurrentNo-loadcurrentInverter modelXD / HH HVFNC1S-1001P 8.5
E6581090K-911 Table of input terminal functions 1FunctionNo.Code Function Action0- No function is assigned No action1ST Standby terminal ON : Standby,
E6581090K-1011 Table of input terminal functions 2FunctionNo.Code Function Action29 R+SS4Combination of reverse run and presetspeed command 4ON : Simu
E6581090K-1111 Table of output terminal functions 1FunctionNo.Code Function Action0LL Frequency lower limitON : Output frequency higher than NN settin
E6581090K-1211 Order of precedence of combined functions XX: Impossible combination, X: Invalid, +: Valid under some conditions, O: Valid, @: Prior
E6581090L-11212. Specifications12.1 Models and their standard specifications Standard specificationsItem SpecificationInput voltage 3-phase 200VApplic
E6581090L-212Item SpecificationInput voltage1-phase 100VApplicable motor (kW)0.1 0.2 0.4 0.75 1.5 2.2TypeVFNC1SForm1001P 1002P 1004P 1007P - -Capacity
E6581090L-312Item SpecificationControl system Sinusoidal PWM controlRelated output voltageAdjustable of output voltage in base frequency setting by th
E6581090L-41212.2 External dimensions/weights External dimensions/weightsDimensions (mm)Input voltageApplicablemotor (kW)TypeWHDW1H1D1DrawingApprox.we
E6581090M-11313.Before making a service call – Trip information and remedies13.1 Trip causes/warnings and remediesWhen a problem arises, diagnose it i
E6581090A-41Note 1: When installing the inverter where the ambient temperature will rise above 40°C, detachthis caution label.An example of a caution
E6581090M-213(Continued)ErrorcodeAlarmcodeProblem Possible causes RemediesQR 000B Overvoltage duringdeceleration• The deceleration time FGE istoo sho
E6581090M-313(Continued)ErrorcodeAlarmcodeProblem Possible causes Remedies*GRJ0008 Input phase failure• A phase failure occurred in theinput line of
E6581090M-413(Continued)ErrorcodeAlarmcodeProblem Possible causes RemediesG 0033 CPUcommunicationserror• A communications error occursbetween contr
E6581090M-513(Continued)ErrorcodeProblem Possible causes RemediesUVQR Momentary powerfailure slowdownstop prohibitionfunction activated• The slowdown
E6581090M-61313.2 Restoring the inverter from a tripDo not reset the inverter when tripped because of a failure or error before eliminating the cause.
E6581090M-71313.3 If the motor does not run while no trip message is displayed ...If the motor does not run while no trip message is displayed, follow
E6581090M-81313.4 How to determine the causes of other problemsThe following table provides a listing of other problems, their possible causes and rem
E6581090N-11414. Inspection and maintenanceDangerMandatory• The equipment must be inspected every day.If the equipment is not inspected and maintained
E6581090N-21414.2 Periodical inspectionMake a periodical inspection at intervals of 3 or 6 months depending on the operating conditions.DangerMandator
E6581090N-314 Replacement of expendable partsThe inverter is composed of a large number of electronic parts including semiconductor devices.The follow
E6581090A-51Note: The self-up (self-lifting) terminals of VFNC1 are constructed with plastic body and screws,therefore please take following precautio
E6581090N-41414.3 Making a call for servicingFor the Toshiba service network, refer to the back cover of this instruction manual. If defectiveconditi
E6581090O-11515. WarrantyAny part of the inverter that proves defective will be repaired and adjusted free of charge under thefollowing conditions:1.
E6581090P-11616. Disposal of the inverter WarningMandatory• If you throw away the inverter, have it done by a specialist in industry wastedisposal*
TOSVERT VF-nC1 Instruction ManualIndustrial InverterTOSHIBA INTERNATIONAL CORPORATION13131 West Little York RD., Houston, TX 77041, U.S.ATEL: +1-713-
E6581090A-61[Main circuit input terminals][Main circuit output terminals][Main circuit input terminals][Main circuit output terminals]VFNC1S-1001P~100
E6581090A-71[Main circuit input terminals][Main circuit output terminals][Main circuit input terminals][Main circuit output terminals]VFNC1S-1007PVFNC
E6581090A-81Sizes of connectable wiresSolid wire: 0.3 to 1.5 (mm2)Stranded wire: 0.3 to 1.5 (mm2)(AWG: 22 to 16)Sheath strip length: 6 mmDriver bit si
E6581090A-911.4 Notes on the application1.4.1 MotorsWhen the VF-nC1 and the motor are used in conjunction, pay attention to the following it
E6581090A-101Loads that generate negative torqueWhen combined with loads that generate negative torque the protection for overvoltage andovercurrent o
E65810901II. Safety precautionsThe items described in these instructions and on the inverter itself are very important so that youcan use the inverter
E6581090A-111Circuit interrupting when two or more inverters are used on the same power line.MCCB1MCCBn+1MCCB3MCCB2INV1INV2INVn(circuitinterrupting fu
E6581090A-121Remedies:1. Reduce PWM carrier frequency.The setting of PWM carrier frequency is done with the parameter H.2. Use high frequency remed
E6581090A-1311.4.4 Installation Installation environmentThe VF-nC1 Inverter is an electronic control instrument. Take full consideration to
E6581090A-141• Operate in areas where ambient temperature ranges from -10°C to 50°C. However, wheninstalling the inverter where the ambient temperatur
E6581090A-151 How to install DangerProhibited• Do not install and operate the inverter if it is damaged or any component is missing.This can result i
E6581090A-161 Calorific values of the inverter and the required ventilationThe energy loss when the inverter converts power from AC to DC and then bac
E6581090A-171 Installing more than one unit in a cabinetIf you are installing two or more inverters in one cabinet, pay attention to the following.• I
E6581090B-122. Connection DangerDisassemblyprohibited• Never disassemble, modify or repair. This can result in electric shock, fire andinjury. For re
E6581090B-22 WarningProhibited• Do not attach devices with built-in capacitors (such as noise filters or surgeabsorber) to the output (motor side) te
E6581090B-32Main circuitR/L1S/L2T/L3P0 PA PCDC reactor(DCL: option)U/T1V/T2W/T3IMVF-nC1FLCFLBFLAP5VI/S3*2 *3CCFRS1S2CCFM/OUT*2CC+-MeterP1
E65810902I General operation DangerSee itemDisassemblyprohibited• Never disassemble, modify or repair. This can result in electric shock, fire and in
E6581090B-42Main circuitR/L1S/L2T/L3P0 PA PCDC reactor(DCL: option)U/T1V/T2W/T3IMVF-nC1FLCFLBFLAFRS1S2CCFM/OUT*2CC+-MeterConnector foropt
E6581090B-52Main circuitR/L1S/L2T/L3P0 PA PCDC reactor(DCL: option)U/T1V/T2W/T3IMVF-nC1FLCFLBFLAP5VI/S3*2 *3CCFRS1S2P15FM/OUT*2CC+-MeterC
E6581090B-62Main circuitR/L1S/L2T/L3P0 PA PCDC reactor(DCL: option)U/T1V/T2W/T3IMVF-nC1FLCFLBFLAFRS1S2P15FM/OUT*2CC+-MeterRyConnector for
E6581090B-722.3 Description of terminals2.3.1 Main circuit terminalsThis diagram shows an example of wiring of the main circuit. Use op
E6581090B-82FLAFLBFLCCCCCCCS2RS1FP5FM/OUTVI/S3P152.3.2 Control circuit terminals (sink logic (common: CC))The control circuit terminal
E6581090B-92Ter mi nal symbolInput/outputFunction Specifications Inverter internal circuitFM/OUTOutputMultifunction programmableoutput.Standard defaul
E6581090B-102Output terminals cannot be switched between sink logic and source logic.See the figures below for connection to sink logic and source log
E6581090C-133. Simple operation DangerProhibited• Do not touch inverter terminals when electrical power is connected to the invertereven if the motor
E6581090C-233.1 Simple operation of the VF-nC1The procedures for setting operation frequency and the methods of operation can be selected fromthe foll
E6581090C-333.1.1 How to start and stop(1) Start and stop using the operation panel keys (EOQF : )Use the RUN and STOP keys on the op
E65810903I Transportation Installation DangerSee itemProhibited• Do not install or operate the inverter if it is damaged or any component is miss
E6581090C-43(2) Setting the frequency using the operation panel (HOQF : )Set the frequency from the operation panel.ً: Moves the frequency upٕ: Mo
E6581090C-532) Setting the frequency using input voltage (0-10V)★Voltage signalSetting frequency using voltage signals(0-10V). For more detailed infor
E6581090D-144. Basic VF-nC1 operationsThe VF-nC1 has the following three monitor modes.Standard monitor mode :The standard inverter mode. This mode is
E6581090D-244.1 How to set parametersThe standard default parameters are programmed before the unit is shipped from the factory.Parameters can be divi
E6581090D-344.1.1 How to set a setup parameterSet the setup parameter according to the logic for control input signals used and the bas
E6581090D-444.1.2 How to set the basic parametersAll of the basic parameters can be set by the same step procedures.[Steps in key entry
E6581090D-544.1.3 How to set extended parametersThe VF-nC1 has extended parameters to allow you to make full use of its functions. All e
E6581090D-64 Example of parameter settingThe steps in setting are as follows. (Example of changing the starting frequency selectionH from to
E6581090D-74 How to use the wizard functionHere are the steps to follow to set parameters, using the wizard function. (When the basic settingwizard (C
E6581090D-84(2) Searching for a history of changes, using the history function (CWJ) How to use the history f unctionKey operated LED display Operatio
E65810904I DangerSee itemMandatory• Electrical construction work must be done by a qualified expert.Connection of input power by someone who does n
E6581090D-94(3) Searching for and changing parameters, using the user parameter group function ITW How to search for and change parametersFollow the
E6581090D-1044.1.5 Parameters that cannot be changed while runningFor reasons of safety, the following parameters have been set up so
E6581090D-1144.1.6 Returning all parameters to standard default settingSetting the standard default setting parameter V[R to 3, all pa
E6581090E-155. Basic parametersBasic parameters refer to parameters you have to set first before using the inverter.5.1 Selecting an operation mode E
E6581090E-25☆The following control input terminals are always operative, no matter how the EOQF parameter(command mode selection) and the HOQF paramet
E6581090E-35 Adjustment scale with meter adjustment HO parameterConnect meters as shown below.FM/OUTCCMeter: frequencymeter(default setting)VF-nC1The
E6581090E-455.3 Standard default setting V[R : Standard setting mode selectionTitle FunctionAdjustment rangeDefault settingV[RStandard settingmod
E6581090E-555.4 Selecting forward and reverse runs (operation panel only) HT : Forward/reverse selection (Operation panel)[Parameter setting]Title
E6581090E-655.6 Maximum frequency HJ : Maximum frequency (Hz)Output frequency (Hz)When HJ = 80HzWhen HJ = 60Hz80Hz60Hz0 100% Frequ
E6581090E-755.8 Base frequency XN : Base frequency 1 (Hz)Note: This is an important parameter that determines the constant torque control area.Ou
E65810905I WarningSee itemProhibited• Observe all permissible operating ranges of motors and mechanical equipment. (Refer tothe motor's instruc
E6581090E-851) Constant torque characteristic Setting of V/F control mode selection RV to (V/F constant)This setting is applied to loads, such as c
E6581090E-955.10 Setting the electronic thermal QNO : Electronic thermal protection characteristics VJT : Motor thermal protection level 1 (%)
E6581090E-105Note: The motor overload protection start level is fixed at 30Hz.VJT×0.55VJT×1.0Output frequency (Hz)Output current reduction factor [%]0
E6581090E-115 Motor 150%-overload time limit : H Using the H parameter (motor 150%-overload withstanding time), you can set the time(betwee
E6581090E-125☆SS3 (preset speed 3) and SS4 (preset speed 4) are not assigned to any terminals at the factory.Before use, therefore, assign SS3 and SS4
E6581090F-166. Extended parametersExtended parameters are used for sophisticated operation, fine adjustment and other specialpurposes. Change paramete
E6581090F-26Output frequency [Hz]Time [sec] HLow speed signal output: 4FM/OUT terminal (H)FL terminal (H)ONOFFONOFF0Set frequencyLow speed re
E6581090F-36•FunctionThis parameter is used to switch the function of the VI/S3 terminal between analog signal inputand contact signal input.•Function
E6581090F-46 Setting of contact input terminal functionTer mi na lsymbolTitle FunctionAdjustmentrangeDefault setting– H Analog input/logic input fu
E6581090F-56• FunctionThis parameter is used to switch between sink logic (negative common) and source logic(positive common).3) Sink logic/source log
E65810906IAttach warning labelsShown here are examples of warning labels to prevent, in advance, accidents in relation toinverters, motors and other e
E6581090F-666.2.6 Changing the function of an output terminal H : Output terminal selection 1 (OUT/FM) H : Output terminal selec
E6581090F-76• FunctionThese parameters are used to switch between two different types of motors connectedto the inverter or to change the characteris
E6581090F-866.4 Analog signals for frequency setting6.4.1 Setting frequency command characteristics H : Analog input/logic input
E6581090F-961) Adjustment of 0~10Vdc voltage inputVI terminal•The output frequencywith respect to thevoltage input is adjustedaccording to the selecte
E6581090F-1066.5 Operation frequency6.5.1 Starting frequency H : Starting frequency setting (Hz)• FunctionThe frequency set with the
E6581090F-1166.6 DC braking6.6.1 DC braking H : DC braking starting frequency (Hz) H : DC braking current (%) H : DC brak
E6581090F-1266.7 Jump frequency – Jumping resonant frequencies H : Jump frequency (Hz) H : Jump width (Hz)• FunctionResonance due to the n
E6581090F-136Reduction in rated load currentWhen the PWM carrier frequency is set above 4kHz, the rated current needs to be decreased.Carrier frequenc
E6581090F-146Title Function Adjustment range Default settingHAuto-restart controlselection0: Disabled1: At auto-restart after momentary stop2: When
E6581090F-1566.10.2 Regenerative power ride-through control/slowdown stop control H : Regenerative power ride-through control• Functio
E6581090i― Contents ―I. Safety precautions・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 11. Read first・・・・・・・・・・・・・・・・・・・・・・・・・・・・
E6581090F-166Here are typical causes of tripping and the corresponding retry processes.Cause oftrippingRetry process Canceling conditionsMomentarypowe
E6581090F-1766.11 Performing PI control H : PI control H : Proportional (P) gain H : Integral (I) gain•FunctionThese parameters are
E6581090F-1864) Adjusting the PI control gain levelAdjust the PI control gain level according to the process quantity, the feedback signal and the obj
E6581090F-1966.12 Improving torque and speed characteristics6.12.1 Setting motor constants RV : V/F control mode selection XN : Base
E6581090F-206★Enabled if the RV parameter (V/F control mode selection) is set to 3 (slip correction)H : Used to set the rated current (A) of the mo
E6581090F-2162) Changing the acceleration/deceleration time by adjusting the contact input signal– Changing the acceleration/deceleration time, using
E6581090F-2266.14.2 Inverter trip retention H : Inverter trip retention selection• FunctionThis parameter is used to prevent the tripp
E6581090F-236(An example of terminal assignment) Assigning the trip stop function to the R terminalTitle FunctionAdjustment range Default settingH
E6581090F-246• FunctionAn over-torque alarm signal is put out if a torque current exceeding the level set with H(over-torque alarm level) flows for
E6581090F-256<Example of operation>1) If function 12 (OT: over-torque detection) is assigned to the FM/OUT terminal,using the output terminal se
E6581090ii8.2 Display of trip information ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ H-39. Taking measures to satisfy the CE / UL / CSA ・
E6581090F-2666.14.9 Analog input disconnection detection H : Analog input disconnection detection•FunctionThis parameter is used to d
E6581090F-276* Using H, the following parameters can be converted.• A display Display of the monitored current• V display Display of the monitored
E6581090F-2866.15.3 Changing the standard monitoring item H : Selection of monitor display selection• FunctionThis parameter is used to
E6581090F-296 Communications parameters (Common serial options)The data transfer rate, parity type, inverter ID number and communication error trip ti
E6581090F-306<Selective communications>When an operation frequency command is sent from the host computer to No. 3 inverterHost computerINVNo.29
E6581090G-177. Variety of operation7.1 Setting the operation frequencyApplied operation can be performed by selecting the inverter frequency setting,
E6581090G-27(5) Input current setting (4 to 20mAdc) (6) Preset-speed settingFRS1S2VI/S3P15P5CCRUNSTOPFR(SS4)S1S2VI/S3P15P5CCRUNSTOPCurrentsignalHOQF
E6581090G-377.2 Setting the operation modeApplied operation can be performed by selecting the operation mode. To set the operation mode,use the basic
E6581090H-188. Monitoring the operation status8.1 Status monitor modeIn this mode, you can monitor the operation status of the inverter.To d i s p l a
E6581090H-28(Continued)ItemdisplayedKeyoperatedLEDdisplayCommunicationNo.DescriptionCPU1versionX FE08 The version of the CPU1 is displayed.CPU2vers