E6581402cTOSVERT VF-FS1 seriesBACnet®option unitInstruction ManualNOTICE1. Make sure that this instruction manual is delivered to the end user of BACn
E6581402c-9-3.2. Description of terminals<Control terminals specification>TerminalsymbolFunction Electrical specifications Internal circuitsB Co
E6581402c-10-3.3. Network cable connectionConnect the BACnet network cable to communication option as follows.Title DescriptionWire type Shielded twis
E6581402c-11-3.5. Wiring of a control terminalObserve the following when wiring.-Use0.3to1.5mm2solid/stranded wire (AWG 22 to 16) for control cables.-
E6581402c-12-4. Parameters4.1. Communication parametersSet up the inverter parameters as follows. To update, reset the power of inverter. If thesepara
E6581402c-13-5. Spe cifications< Environmental specification >Item SpecificationService environment Conforms to VF-FS1Operation temperature Conf
E6581402c- 14E -6. WarrantyAny part of BACnet communication option that is proved to be defective will be repaired free ofcharge under the following c
E6581402c-1-Safety precautionsOn the inverter and in its instruction manual, important information is contained for preventinginjuries to users, damag
E6581402c-2-Limitation of useSafety precautionNever use this unit wit h any device other than TOSVERT VF-FS1 series inverters. Doing so may causean ac
E6581402c-3-WiringWarningMandatoryElectrical construction work must be done by a qualified expert.Connection of input power by someone who does not ha
E6581402c-4-PrefaceThank you for purchasing the³BACnet®option(BCN002Z)´ for TOSVERT VF-FS1 inverter. ByInstalling this board into the VF-FS1, data com
E6581402c-5-Table of Contents1. Overview 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 62. Names and functions 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯
E6581402c-6-1. OverviewThe BACnet (BCN002Z) interface allows the VF-FS1 inverter to be connected into a BACnet network.BACnet MS/TP supports a maximum
E6581402c-7-2.3. LED indicatorThe option has two LEDs. Those functions are below table.StateLEDsCommentAGreen LED : OFFRedLED :Flashing5timesin1second
E6581402c-8-3. Installation and Setup3.1. Installation methodInstall the BACnet communication option to VF-FS1 as follows.(1) Turn off the input power