TOSHIBAUNINTERRUPTIBLE POWER SYSTEMSINGLE PHASE - .6/.8/1.0/1.2 kVASINGLE PHASE - .6/.8/1.0 kVA PLUSMarch, 2003Part # 46370-002MANUFACTURED IN THE U.S
TOSHIBAModel Capacity Manufacturer Type Quantity600 VA / 600 VA PlusYuasa NP4-12FR 5800 VA / 800 VA Plus1000 VA / 1000 VA PlusYuasa NPH5-12FR 51200 VA
TOSHIBA1.0 Product Description1.1 Theory of OperationAn uninterruptible power supply is a system that is installed between the commercialpower and the
TOSHIBA2.0 Inspection/Storage/Disposal2.1 Inspection of the new UPS equipmentUpon receipt of the UPS, a careful inspection for shipping damage should
TOSHIBA3 - 13.0 Precautions3.1 Installation Precautions (General)1) Install the unit in a well ventilated location; allow at least 10 cm (4 inches) on
TOSHIBA3.0 Precautions3.2 Prestart Precautions1) Before connecting the UPS to a power source; move the operation switch(STOP/RUN), on the front panel
TOSHIBAMODEL NUMBER UE1A1A006C6 UE1A1A008C6 UE1A1A010C6CAPACITY 600 VA (0.42 kW) 800 VA (0.56 kW) 1000 VA (0.7 kW)Input Input voltage Single phase, 1
TOSHIBAMODEL NUMBER UE1A1A012C6CAPACITY 1200 VA (0.84 kW)Input Input voltage Single phase, 120 Vac, +10% to -30% (*)Input frequency 45 to 65 HzInput
TOSHIBAMODEL NUMBER UE1A1A006C6T UE1A1A008C6T UE1A1A010C6TCAPACITY 600 VA (0.42 kW) 800 VA (0.56 kW) 1000 VA (0.7 kW)Input Input voltage Single phase
TOSHIBA5.0 Operating the UPS5.1 Operation Modes5.1.1 AC Input Mode (normal operation)Power flow in AC input modeThe above illustration shows circuit p
TOSHIBA5.0 Operating the UPS5.1 Operation Modes5.1.3 Circuit-bypass modePower flow in circuit-bypass mode.If the UPS unit is severely overloaded or de
TOSHIBA
TOSHIBA5.0 Operating the UPS5.3 Operation Monitoring5.3.1 Visual Indicator FunctionsThe following LED (light emitting diode) indicators are located on
TOSHIBAOutput Display Status ExplanationDuring battery backup allgreen lamps flash and thered Backup lamp is litcontinuously. As thebatteries discharg
TOSHIBA5 - 55.0 Operating the UPS (Cont'd)5.6 Battery RechargingThe graph below shows the typical voltage requirements for recharging the UPS uni
TOSHIBA5 - 65.0 Operating the UPS5.7 Battery Backup TimeThe UPS unit's batteries provide about 5-12 minutes of back-up time depending on thecapac
TOSHIBA6 - 16.0 UPS Control Interface6.1 DB25 Connector PinoutRS-232C serial communication and Dry Contacts are both standard features availablethroug
TOSHIBA6.0 UPS Control Interface6.2 RS-232C Serial Communication InterfaceThe available data from the UPS, via RS-232C communication, is shown below:O
TOSHIBAFault Display status Probable cause Corrective actionRemove cause ofOutput low Inverter fault or short short circuit. If none isvoltage circuit
TOSHIBAFault Display status Probable cause Corrective actionDC Inverter faultovercurrentDC Chopper faultovervoltageContact your Toshibaservice represe
TOSHIBA8.0 Preventive and Scheduled Maintenance/Parts Replacement8.1 Preventive MaintenanceToshiba's 1500 and 1500 Plus Series of uninterruptible
TOSHIBAFuse ratingModel Amp rating Fuse model no.600 VA 15.0A LittleFuse 314015800 VA 15.0A LittleFuse 3140151000 VA 15.0A LittleFuse 3140151200 VA 15
TOSHIBAThe instructions contained in this manual are not intended to cover all of the detailsor variations in equipment, nor to provide for every poss
TOSHIBA8.0010.00Input powercord connectorFuseComputerInterfaceConnectorOutputReceptaclesAir Vents20.389.0 External Dimensions/Shipping Weights/Panel L
TOSHIBA9.0 External Dimensions/Shipping Weights/Panel Layout9.2 Panel Layout9.3 Shipping WeightsUPS Shipping WeightModel Pounds Kilograms600 VA 48.8 2
TOSHIBATOSHIBA INTERNATIONAL CORPORATIONINDUSTRIAL DIVISION13131 West Little York Rd., Houston Texas 77041Tel: [800] 231-1412 Fax: [713] 466-8773 Tele
TOSHIBACONTENTSSECTION PAGEDisclaimer ... iContents ...
TOSHIBACONTENTS (Cont'd)SECTION PAGE5.0 Operating the UPS (cont'd) ... 5-15
TOSHIBAivINTRODUCTIONThank you for purchasing the 1500/1500 Plus Series UPS. This Series features the verylatest state of the art microprocessor techn
TOSHIBAvGENERAL SAFETY INSTRUCTIONSWarnings in this manual appear in any of four ways:1) Danger - The danger symbol is a lightning bolt mark enclosed
TOSHIBASAVE THESE INSTRUCTIONS- This manual contains important instructionsthat should be followed during the installation and maintenance of the UPS
TOSHIBAIMPORTANT SAFETY INSTRUCTIONSInstallation and servicing of batteries should be performed by personnelknowledgeable of batteries and the require