Toshiba G9000 User Manual

Browse online or download User Manual for Tools Toshiba G9000. Toshiba G9000 User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - G9000 SERIES

UNINTERRUPTIBLE POWER SYSTEM (UPS) G9000 SERIES INSTALLATION AND OPERATION MANUAL 480/480 V 80/100/160/225/300/500/750 kVA

Page 2

iv G9000 Installation and Operation Manual Figure 2.18 The connector (CN1) of PSAU-60 (PS1)...

Page 3

INDUSTRIAL DIVISION 13131 West Little York Rd., Houston, TX 77041 Tel: 713/466-0277 Fax 713/466-8773 US 877/867-8773

Page 4

G9000 Installation and Operation Manual 1 How to use this Manual This manual is designed for ease of use, giving the user easy and quick referen

Page 5 - IMPORTANT NOTICE

2 G9000 Installation and Operation Manual 1 INTRODUCTION The Toshiba Uninterruptible Power Supply System (UPS) is designed to provide many year

Page 6 - Purpose and Scope of Manual

G9000 Installation and Operation Manual 3 In no event will TOSHIBA be responsible or liable for either indirect or consequential damage or i

Page 7 - Table of Contents

4 G9000 Installation and Operation Manual The UPS is to be installed in a controlled environment. Improper storage and installation environ

Page 8 - List of Tables

G9000 Installation and Operation Manual 5 This UPS does not include a Bypass input circuit breaker (MCCB) to protect the bypass circuit. Th

Page 9 - List of Figures

6 G9000 Installation and Operation Manual 1.2 GENERAL The Toshiba G9000 UPS is designed to provide continuous and clean electrical power to a c

Page 10

G9000 Installation and Operation Manual 7 1.3 DEFINITIONS UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS Module Cab

Page 11 - How to use this Manual

8 G9000 Installation and Operation Manual 1.4 OPERATION OVERVIEW The UPS provides two power paths between the utility source and the critical lo

Page 12 - 1.1.1.1.1.1.1.1

G9000 Installation and Operation Manual 9 In the event of a UPS module failure during Parallel Operation, the critical load power will be contin

Page 13 - WARNING 2

G9000 Installation and Operation Manual

Page 14 - WARNING 3

10 G9000 Installation and Operation Manual In the event of a load overcurrent, the UPS transfers to bypass without interruption to the critical lo

Page 15 - WARNING 4

G9000 Installation and Operation Manual 11 When power is restored after a low battery shutdown, the UPS converter(s) automatically restarts opera

Page 16

12 G9000 Installation and Operation Manual FIGURE 1.4.1 UPS Parts Location (80,100kVA) UPS module Front ViewCPMCCPMSEMB88FInverter, Converter

Page 17

G9000 Installation and Operation Manual 13 FIGURE 1.4.3 UPS Parts Location (300kVA) a) UPS cabinet – Front View b) Door Backside (Main Cabinet)

Page 18

14 G9000 Installation and Operation Manual FIGURE 1.4.4 UPS Parts Location (500kVA) a) UPS cabinet – Front View b) Backside of Left Door Landing

Page 19

G9000 Installation and Operation Manual 15 FIGURE 1.4.5 UPS Parts Location (750kVA) a) UPS cabinet – Front View b) Backside of Left Door 1. LCD

Page 20

16 G9000 Installation and Operation Manual FIGURE 1.5 Display PCB DPAU-81 CNV.SWswitch11. SW1RESET switchSTART buttonSTOP button12. SW5TEST

Page 21

G9000 Installation and Operation Manual 17 FIGURE 1.7.1 Parallel I/F PCB IFAU-08 (80-225kVA) FIGURE 1.7.2 Parallel I/F PCB IFAU-09 (

Page 22 - UPS module Front View

18 G9000 Installation and Operation Manual FIGURE 1.8 MAIN PCB UPGR-M 15. SW352L S/W switch14. SW2BOOT switch11. SW1RESET switch Description

Page 23

G9000 Installation and Operation Manual 19 4. Main PCB UPGR-M (Figure 1.8): Switches on UPGR-M board : FOR SERVICE PERSONNEL ONLY - (11) SW1 (R

Page 24

G9000 Installation and Operation Manual G9000 SERIES INSTALLATION AND OPERATION MANUAL 480/480 V 80/100/160/225/300/500/750 kVA Document No.

Page 25

20 G9000 Installation and Operation Manual 1.5 SPECIFICATIONS The UPS nameplate displays the rated kVA as well as nominal voltages and currents

Page 26

G9000 Installation and Operation Manual 21 TABLE 1.4 UPS Module Information a) Overall Dimension UPS [kVA] Width [in.] (mm) Depth [in.] (mm)

Page 27 - IFAU-08

22 G9000 Installation and Operation Manual TABLE 1.5.a Detail of Specifications Rated Output kVA 80 100 160 225 300 500 750 Rated Output kW

Page 28

G9000 Installation and Operation Manual 23 Rated Output kVA 80 100 160 225 300 500 750 Batt. Capacity Required at Full Load Output 75

Page 29

24 G9000 Installation and Operation Manual Rated Output kVA 80 100 160 225 300 500 750 Enclosure NEMA 1 Audible Noise 70 dB @ 1 m 73 dB @ 1 m

Page 30

G9000 Installation and Operation Manual 25 TABLE 1.6 Rating of Contactors, Breakers and Fuses NUMBER APPLICATION OUTPUT CAPACITY O

Page 31

26 G9000 Installation and Operation Manual 2 OPERATOR CONTROLS AND INDICATORS The G9000 Series operator controls and indicators are located as

Page 32

G9000 Installation and Operation Manual 27 2.1 LED DISPLAY 1) Load on inverter [ LOAD ON INVERTER ](green) Illuminates when power is suppli

Page 33 - ENVIRONMENTAL

28 G9000 Installation and Operation Manual 2.3 LIQUID CRYSTAL DISPLAY (8) The Liquid Crystal Display (LCD) touch panel indicates power flow, mea

Page 34 - MONITORING

G9000 Installation and Operation Manual 29 FIGURE 2.3.1 Startup/Shutdown Guidance FIGURE 2.3.2 Startup guidance

Page 35

G9000 Installation and Operation Manual

Page 36

30 G9000 Installation and Operation Manual FIGURE 2.4.2 Output values FIGURE 2.4.3 Values in Battery operation

Page 37

G9000 Installation and Operation Manual 31 D) LOG MENU (FIGURES 2.6.1 to 2.6.3) This LOG MENU displays two Touch icons in EVENT LOG and BATTE

Page 38

32 G9000 Installation and Operation Manual 2.3.2 Input Power Failure During an Input Power Failure, the UPS inverter will be powered by the UPS b

Page 39

G9000 Installation and Operation Manual 33 1) MESSAGE The display shows a fault code, the description of the fault and a guidance of what act

Page 40

34 G9000 Installation and Operation Manual 2.4 EXTERNAL SIGNAL TERMINAL BLOCK The UPS is equipped with a series of input/output terminals for e

Page 41

G9000 Installation and Operation Manual 35 FIGURE 2.10.2 External Signal Terminal Block (NEC Class2) TN1 (User supplied dry contac

Page 42

36 G9000 Installation and Operation Manual A) Output Contacts (for external alarm annunciation) Output contacts consist of form “A”(NO) dry typ

Page 43

G9000 Installation and Operation Manual 37 The UPS is equipped with a selectable output contact feature. The above alarms are the default settin

Page 44

38 G9000 Installation and Operation Manual Details of input contacts for remote access : TN1 Terminals 7 to 8 Remote "Inverter Start"

Page 45 - contact)

G9000 Installation and Operation Manual 39 2.5 RemotEyeII INTRODUCTION The “RemotEyeII”* is available as a UPS system monitoring tool. The Remo

Page 46

G9000 Installation and Operation Manual The Instructions contained in this manual are not intended to cover all of the details or variations in eq

Page 47 - PROHIBIT

40 G9000 Installation and Operation Manual FIGURE 2.13.2 Configuration of the RemotEyeII (300kVA) * Consult Toshiba International Co

Page 48 - CAUTION

G9000 Installation and Operation Manual 41 FIGURE 2.13.3 Configuration of the RemotEyeII (Overview: 500-750kVA) * Consult Toshiba Inte

Page 49

42 G9000 Installation and Operation Manual The Power Supply PCB (PSAU-60, designated as PS1) and the Cable1 (designated as 3BBA0083P001) are equip

Page 50

G9000 Installation and Operation Manual 43 The parts (included RemotEyeII) for UPS monitoring are listed below. TABLE 2-1 Parts list for UPS mon

Page 51

44 G9000 Installation and Operation Manual 2.6 CONNECTOR DEFINITION FIGURE 2.18 The connector (CN1) of PSAU-60 (PS1) FIGURE 2.19 The t

Page 52 - RemotEyeII

G9000 Installation and Operation Manual 45 3 INSTALLATION AND OPERATION 3.1 TRANSPORTATION AND INSTALLATION TABLE 3.1 How to transport and i

Page 53

46 G9000 Installation and Operation Manual D) External Battery Supply Please refer to the following when installing and maintaining batteries:

Page 54

G9000 Installation and Operation Manual 47 After the completion of the input power cables connection: With a phase rotation meter, check that th

Page 55

48 G9000 Installation and Operation Manual (3) Connect the external signal terminal block as desired. Refer to Section 2.4 and Figure 2.10 for f

Page 56

G9000 Installation and Operation Manual 49 TABLE 3.4 Recommended Cable Sizes Input Side Output Side Bypass Side DC Input Side

Page 57 - REQUIRED

G9000 Installation and Operation Manual Purpose and Scope of Manual This manual provides information on how to safely install, operate, and main

Page 58

50 G9000 Installation and Operation Manual TABLE 3.5 Crimp Type Compression Lug WIRE SIZE WIRE STRAND RECOMMENDATION CRIMP TOOL REQUIRED BURNDY

Page 59

G9000 Installation and Operation Manual 51 FIGURE 3.2.1. Diagram of input/output bus bars and terminal blocks (80-225kVA) Location of bus bars a

Page 60 - Crimp Type Compression Lug

52 G9000 Installation and Operation Manual FIGURE 3.2.2. Diagram of input/output bus bars and terminal blocks (300kVA) Location of bus bars

Page 61

G9000 Installation and Operation Manual 53 FIGURE 3.2.3. Diagram of input/output bus bars and terminal blocks (500kVA) Location of bus bars and

Page 62 - 78.7" (2000)

54 G9000 Installation and Operation Manual FIGURE 3.2.4. Diagram of input/output bus bars and terminal blocks (750kVA) Location of bus bars

Page 63

G9000 Installation and Operation Manual 55 FIGURE 3.3.1 Detail of the main cabinet bus bars (300kVA) BUS BAR DETAIL(TOP VIEW)BUS BAR DETAIL(

Page 64

56 G9000 Installation and Operation Manual FIGURE 3.3.2 Detail of the main cabinet bus bars (500kVA) BUS BAR DETAIL(TOP VIEW)BUS BAR DE

Page 65 - (TOP VIEW)

G9000 Installation and Operation Manual 57 FIGURE 3.3.3 Detail of the main cabinet bus bars (750kVA) BUS BAR DETAIL(TOP VIEW)

Page 66

58 G9000 Installation and Operation Manual FIGURE 3.4.1 Bus bar connection between main cabinet and landing cabinet (300kVA) LandingCab

Page 67

G9000 Installation and Operation Manual 59 FIGURE 3.4.2 Bus bar connection between main cabinet and landing cabinet (500kVA) BUS BAR CONNECT

Page 68 - ALTERNATE

G9000 Installation and Operation Manual i Table of Contents List of Tables ...

Page 69

60 G9000 Installation and Operation Manual FIGURE 3.4.3 Bus bar connection between main cabinet and landing cabinet (750kVA) LandingCabi

Page 70

G9000 Installation and Operation Manual 61 FIGURE 3.5 Diagram of Power Wire & Control Wire Inter-Connect between UPS and Battery UVR

Page 71 - DC Breaker for Battery

62 G9000 Installation and Operation Manual FIGURE 3.6 Diagram of Power Wire Connections (Parallel System Configuration) 52L1 UPS Bre

Page 72

G9000 Installation and Operation Manual 63 FIGURE 3.7.1 Diagram of Power Wire & Control Wire Connections for 4 units in MMS Configuration

Page 73

64 G9000 Installation and Operation Manual FIGURE 3.7.2 Diagram of Power Wire & Control Wire Connections for 2 units in MMS Configuration (30

Page 74

G9000 Installation and Operation Manual 65 FIGURE 3.7.3 Diagram of Power Wire & Control Wire Connections for 3 or 4 units in MMS Configurat

Page 75 - (300-750kVA)

66 G9000 Installation and Operation Manual FIGURE 3.7.4 Diagram of Power Wire & Control Wire Connections for 5 to 8 units in MMS Configuratio

Page 76

G9000 Installation and Operation Manual 67 EMB CPMS CPMC 3.4 OPERATING PROCEDURES For Parallel Operation system, refer to section “D) MMS Sta

Page 77

68 G9000 Installation and Operation Manual B) Shut-down Procedure If a total UPS shutdown is required, verify that the critical load is OFF

Page 78 - WARNING

G9000 Installation and Operation Manual 69 C) Bypass Operation Procedure ** Transfer from Inverter to Bypass 1. Check for “SYNC” on the LC

Page 79

ii G9000 Installation and Operation Manual List of Tables Table 1.1 UPS installation environment ...

Page 80

70 G9000 Installation and Operation Manual D) MMS Start-up Procedure External Circuit Check (Ensure System is in Maintenance Bypass) 1. Verify

Page 81 - 4 RESPONSE TO UPS FAILURE

G9000 Installation and Operation Manual 71 4 RESPONSE TO UPS FAILURE Depress “SILENCE ALARM” icon on Main Menu. Refer to the list of fa

Page 82 - 5 PARTS REPLACEMENT

72 G9000 Installation and Operation Manual 5 PARTS REPLACEMENT Contact Toshiba International Corporation or its authorized service representati

Page 83 - 6 FAULT CODES

G9000 Installation and Operation Manual 73 6 FAULT CODES This section covers fault codes, their description and required action. At time of

Page 84 - Table 6.1 Fault Code

74 G9000 Installation and Operation Manual Failure Code List Table 6.1 Fault Code Note 3 Note 1 Note 2 Code indication Status message Me

Page 85

G9000 Installation and Operation Manual 75 Note 3 Note 1 Note 2 Code indication Status message Meaning Guidance Buzzer External relay

Page 86

76 G9000 Installation and Operation Manual Note 3 Note 1 Note 2 Code indication Status message Meaning Guidance Buzzer External relay c

Page 87

G9000 Installation and Operation Manual 77 Note 3 Note 1 Note 2 Code indication Status message Meaning Guidance Buzzer External relay

Page 88

78 G9000 Installation and Operation Manual Note 3 Note 1 Note 2 Code indication Status message Meaning Guidance Buzzer External relay contact

Page 89

G9000 Installation and Operation Manual 79 Note 3 Note 1 Note 2 Code indication Status message Meaning Guidance Buzzer External relay conta

Page 90 - 7 DAILY INSPECTION

G9000 Installation and Operation Manual iii List of Figures Figure 1.1 Single line diagram – normal operation ...

Page 91

80 G9000 Installation and Operation Manual 7 DAILY INSPECTION Please perform the daily inspection while the UPS is running. The daily inspection

Page 92

G9000 Installation and Operation Manual 81 APPENDIX A Installation Planning Guides (IPG) Installation Planning Guide for 80kVA UPS Standard

Page 93

82 G9000 Installation and Operation Manual Installation Planning Guide for 100kVA UPS Standard System: 480V Input, 480V Output General Mechanical

Page 94

G9000 Installation and Operation Manual 83 Installation Planning Guide for 160kVA UPS Standard System: 480V Input, 480V Output General Mechanic

Page 95 - – (3) x 350kcmil

84 G9000 Installation and Operation Manual Installation Planning Guide for 225kVA UPS Standard System: 480V Input, 480V Output General Mechanical

Page 96 - –(4) x 500kcmil

G9000 Installation and Operation Manual 85 Installation Planning Guide for 300kVA UPS Standard System: 480V Input, 480V Output General Mechanic

Page 97 - – (6) x 500kcmil

86 G9000 Installation and Operation Manual Installation Planning Guide for 500kVA UPS Standard System: 480V Input, 480V Output General Mechanical

Page 98

G9000 Installation and Operation Manual 87 Installation Planning Guide for 750kVA UPS Standard System: 480V Input, 480V Output General Mechani

Page 99

88 G9000 Installation and Operation Manual

Page 100 - Printed in Japan

G9000 Installation and Operation Manual 89