Toshiba RAS-10SKV-A User Manual

Browse online or download User Manual for Conditioners Toshiba RAS-10SKV-A. Toshiba RAS-10SKV-A User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - AIR CONDITIONER

FILE NO. SVM-07008-1SERVICE MANUALAIR CONDITIONERSPLIT WALL TYPERevised May, 2007RAS-10SKV-E / RAS-10SAV-ERAS-10SKV-A / RAS-10SAV-A

Page 2 - CONTENTS

– 9 –43˚ to 45˚45˚ to 46˚B ACDTable 3-2-6 Flare and flare nut dimensions for R22Nominaldiameter1/43/81/25/83/4Outer diameter(mm)6.359.5212.7015.8819.

Page 3 - 1. SAFETY PRECAUTIONS

– 10 –3-3. Tools3-3-1. Required ToolsThe service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A ischanged to

Page 4

– 11 –Connect the charge hose to packed valve service port at the outdoor unit’s gas side.Recover the refrigerant, and check no refrigerant remains in

Page 5 - 2. SPECIFICATIONS

– 12 –Gauge manifold[ Cylinder with siphon ] [ Cylinder without siphon ]OUTDOOR unitGauge manifoldOUTDOOR unitRefrigerantcylinderElectronic balanceRef

Page 6

– 13 –Nitrogen gascylinderPipeFlow meterMStop valveFrom Nitrogen cylinderNitrogen gasRubber plug2. Characteristics required for flux• Activated temper

Page 7 - 3. REFRIGERANT R410A

– 14 –4. CONSTRUCTION VIEWS4-1. Indoor Unit 3845250235135 9040 165 451359026290Knock out system58852195Front panelKnock out system860Air inletAir filt

Page 8

FILE NO. SVM-07008− 15 −4-2. Outdoor UnitCLCL

Page 9

– 16 –FILE NO. SVM-070085. WIRING DIAGRAM5-1. Indoor Unit

Page 10 - 45˚ to 46˚

FILE NO. SVM-07008– 17 –5-2. Outdoor Unit

Page 11 - FILE NO. SVM-07008

– 18 –FILE NO. SVM-070086. SPECIFICATION OF ELECTRICAL PARTS6-1. Indoor Unit No. Parts name Type Specifications1 Fan motor (for indoor)

Page 12

CONTENTS1. SAFETY PRECAUTIONS ... 22. SPECIFICATIONS ...

Page 13

FILE NO. SVM-07008– 19 –6-2. Outdoor Unit (RAS-10SAV-E, RAS-10SAV-A)No. Parts name Model name Rating1 SC coil L01 GET-0451 0.6mH, 15A(Noise

Page 14

– 20 –7. REFRIGERANT CYCLE DIAGRAM7-1. Refrigerant Cycle DiagramRAS-10SKV-E / RAS-10SAV-ENOTE :• The maximum pipe length of this air conditioner is 1

Page 15 - 4. CONSTRUCTION VIEWS

– 21 –7-2. Operation Data<Cooling>Model name Standard Indoor Outdoor CompressorRAS- pressure fan mode fan mode revolutionIndoor Outdoor P (MPa)

Page 16

– 22 –FILE NO. SVM-07008REMOTE CONTROLRemote ControlOperation ( )Operation Mode Selection AUTO, COOL, DRY, HEAT, FAN ONLYTemperature SettingFan Spe

Page 17

– 23 –FILE NO. SVM-070088-2. Outdoor Unit (Inverter Assembly)For INDOOR UNIT1230V 50HzsignalNoisefilterInputcurrentsensorConverter(AC DC)P.C.B (MCC

Page 18 - 5-2. Outdoor Unit

− 24 −9. OPERATION DESCRIPTION9-1. Outline of Air Conditioner ControlThis air conditioner is a capacity-variable type airconditioner, which uses A

Page 19

– 25 −9-2. Operation Description 1. Basic operation ...

Page 20

– 26 –Item1. BasicoperationOperation flow and applicable data, etc.1. Operation controlDescriptionReceiving the user’s operation condition setup, the

Page 21 - 7. REFRIGERANT CYCLE DIAGRAM

− 27 −Operation ON Setup of remote controllerIndoor fan motor control / Louver control / Operation HzControl (Requierment)Indoor unit controlSending

Page 22

– 28 –Item2. Indoor fanmotor controlOperation flow and applicable data, etc.<In cooling operation>(This operation controls the fan speed at indo

Page 23

– 2 –1. SAFETY PRECAUTIONSFor general public usePower supply cord of outdoor unit shall be more than 1.5 mm2 (H07RN-F or 60245IEC66) polychloroprenes

Page 24

– 29 –Item2. Indoor fanmotor controlOperation flow and applicable data, etc.<In heating operation>Description1) When setting the fan speed to L,

Page 25 - 9. OPERATION DESCRIPTION

– 30 –Item3. CapacitycontrolOperation flow and applicable data, etc.The cooling or heating capacity depending on the load isadjusted.According to diff

Page 26

– 31 –Item5. Release protectivecontrol by tempera-ture of indoor heatexchangerOperation flow and applicable data, etc.<In cooling/dry operation>

Page 27 - • ONE-TOUCH

– 32 –ItemOperation flow and applicable data, etc.Description6. Defrost control(Only in heatingoperation)(This function removes frost adhered to the o

Page 28

HorizontalblowingInclinedblowingBlowingdownwardAir directionInclinedblowingHorizontalblowingInitial setting of "Cooling storage position"Lou

Page 29

– 34 –Item8. ECOoperationOperation flow and applicable data, etc.When pressing [ECO] button on the remote controller, a Economic operation is performe

Page 30

– 35 –Item9. TemporaryoperationOperation flow and applicable data, etc.Pressing [RESET] button starts the temporary opera-tion of [AUTO] operation. Wh

Page 31

– 36 –Item11. Self-CleaningOperation flow and applicable data, etc.1. PurposeThe Self-Cleaning operation is to minimize thegrowth of mold, bacteria et

Page 32

Item11. Self-CleaningfunctionOperation flow and applicable data, etc.• Self-Cleaning diagramDescription12. Self-Cleaningfunction releaseOperation di

Page 33

Item13. Romote-A or BselectionOperation flow and applicable data, etc.Description1. PurposeThis operation is to operate only oneindoor unit using one

Page 34

• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURETO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.• TO PREVENT

Page 35

Item14. QUIET modeOperation flow and applicable data, etc.DescriptionWhen the [QUIET] button is pressed, the fan of the indoor unit will be restricted

Page 36

ItemOperation flow and applicable data, etc.Description17. Hi-POWER ([Hi-POWER] button on the remote controller is pressed)When [Hi-POWER] button is p

Page 37

– 41 –OperationPress [RESET] button for more thanthree seconds. (Less than 10 seconds)MotionsThe unit is on standby.↓The unit starts to operate. The g

Page 38

– 42 –OperationPress [RESET] button for more thanthree seconds. (Less than 10 seconds)MotionsThe unit is on standby.↓The unit starts to operate. The g

Page 39

1111 Infrared signal emitterStart/Stop buttonMode select button (MODE)Temperature button (TEMP)Fan speed button (FANSwing louver button (SWING)Set lou

Page 40

– 44 –4. DRY OPERATION (COOLING ONLY)For dehumidification, a moderate cooling performance is controlled automatically.1. Press MODE : Select Dry

Page 41 - 17. Hi-POWER

− 45 − 9. PRESET OPERATIONSet your preferred operation for future use. The setting will be memorized by theunit for future operation (except air fl

Page 42 - RESET button

– 46 –9-4-3. Name and Functions of Indications on Remote Controller[Display]All indications, except for the clock time indicator, are displayed by pre

Page 43

− 47 −FILE NO. SVM-0700810-1-1. Installation Diagram of Indoor and Outdoor UnitsShield pipeAir filterHookHook(Attach to the front panel.)65 mm or more

Page 44

– 48 −FILE NO. SVM-0700810-1-2. Optional installation parts<Fixing bolt arrangement of outdoor unit>Fig. 9-1-2 Secure the outdoor unit with the

Page 45

– 4 – 2. SPECIFICATIONS2-1. Specifications Unit model Indoor RAS-10SKV-E, RAS-10SKV-AOutdoor RAS-10SAV-E, RAS-10SAV-ACooling capacity (kW) 2.5Cooling

Page 46

– 49 –FILE NO. SVM-07008PartNo.123Part name (Q’ty)Installation plate x 1Wireless remote control x 1Battery x 2Part name (Q’ty)Remote control holder x

Page 47

– 50 –FILE NO. SVM-07008• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating inthe U. S’s A

Page 48 - 3 Batteries

– 51 –FILE NO. SVM-07008-110-2. Indoor Unit10-2-1. Installation place• A place which provides the spaces around theindoor unit as shown in the above d

Page 49

– 52 –FILE NO. SVM-07008<When the installation plate is directly mounted onthe wall>1. Securely fit the installation plate onto the wall byscrew

Page 50

– 53 –FILE NO. SVM-0700810-2-4. Wiring connection<How to connect the connecting cable>Wiring of the connecting cable can be carried outwithout r

Page 51

– 54 –FILE NO. SVM-07008<How to fix the Drains Cap>1) Insert hexagonal wrench (∅4 mm) in a center head.Fig. 10-2-112) Firmly insert drains cap.F

Page 52 - 7 Mounting screw

– 55 –FILE NO. SVM-0700810-3-2. Refrigerant piping connection<Flaring>1. Cut the pipe with a pipe cutter.Fig. 10-3-22. Insert a flare nut into t

Page 53

– 56 –FILE NO. SVM-07008-110-3-3. EvacuatingAfter the piping has been connected to the indoor unit,you can perform the air purge together at once.AIR

Page 54

– 57 –FILE NO. SVM-07008<Stripping length of connection cable>CAUTION• Wrong wiring connection may cause someelectrical parts burn out.• Be sure

Page 55

– 58 –FILE NO. SVM-0700810-3-5. Gas leak testFig. 10-3-10• Check the flare nut connections for the gas leakwith a gas leak detector or soap water.Chec

Page 56

2-2. Operation Characteristic Curve– 5 –FILE NO. SVM-07008<Cooling> <Heating>2-3. Capacity Variation Ratio According to Temperature<Coo

Page 57

– 59 –FILE NO. SVM-07008Inverter coverP. C. board (Soldered surface)Discharging position (Discharging period 10 seconds or more)Plug of soldering iron

Page 58 - RAS-10SKV

– 60 –FILE NO. SVM-0700811-1-3. Operation which is not a trouble (Program operation)For controlling the air conditioner, the program operations are bu

Page 59

– 61 –FILE NO. SVM-0700811-3. Judgment by Flashing LED of Indoor UnitWhile the indoor unit monitors the operation status of the air conditioner, if th

Page 60

– 62 –11-4. Self-Diagnosis by Remote Controller (Check Code)1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis

Page 61

– 63 –FILE NO. SVM-0700811-4-2. Caution at servicing(1) After servicing, push the [ ] button to return to the normal mode.(2) After servicing by the

Page 62

– 64 –FILE NO. SVM-7008Block distinction Operation of diagnosis functionJudgment and actionCheckBlockCheckCause of operationAir conditionerRemarkscode

Page 63

– 65 –OperationMeasureItem by symptomsCheck itemConceivable principle causeParts(D01 ~ D04,C03, T101 and IC12 are defective.• Be sure to disconnect th

Page 64

(2) Power is not turned on though Indoor P.C. board is replaced<Confirmation procedure>YES YESNO NOTo item of “Power is not turned on”.Turn on p

Page 65 - FILE NO. SVM-7008

FILE NO. SVM-07008– 67 –(3) Only the indoor fan does not operate.Replace the fan motor.YESNONOYESYESNONOYESYESYESNONO NOYESDoes the fan stop inno oper

Page 66

<Cause>The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to the inside of the motor.If the P.C. board is soldere

Page 67

– 6 –3. REFRIGERANT R410AThis air conditioner adopts the new refrigerant HFC(R410A) which does not damage the ozone layer.The working pressure of the

Page 68

– 69 –FILE NO. SVM-07008Press [ ]button.Is transmissionmark indicated?Press RESET buttonon remote controlwith tip of pencil.Is receiver onindoor un

Page 69

– 70 –FILE NO. SVM-07008Measure gas pressure.Gas shortagePipe cloggingThermo operation of compressorGas circulation amount is down.Gas leak11-5-2. Wir

Page 70

– 71 –FILE NO. SVM-0700811-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E<Check procedure>NONONONOYESYESYESYESYESGas leakage,discon

Page 71

– 72 –FILE NO. SVM-0700811-7. How to Diagnose Trouble in Outdoor Unit11-7-1. Summarized inner diagnosis of inverter assemblyDiagnosis/Process flowchar

Page 72

– 73 –FILE NO. SVM-07008CheckOperation→ OK if 10MΩ or more →OK if 0.51Ω → 0.57Ω(Check by a digital tester.)a) One or two of threevoltages should be 5

Page 73

FILE NO. SVM-07008(3) Checking procedure.Table 11-6-1No.123456Procedure1. Application of shock voltage.Overload by short-circuit of theparts.1. AC pow

Page 74

– 75 –10030405060708090201000102030 4050Resistance value (k )Temperature (˚C)TD : Discharge temp. sensorTA : Room temp. sensorTC : Heat exchanger temp

Page 75 - 12V and GND

– 76 –FILE NO. SVM-070081 Room temp. (TA) sensorHeat exchanger (TC) sensor2 Remote control3 Louver motor24BYJ484 Indoor fan motorDisconnect the connec

Page 76

– 77 –FILE NO. SVM-070081 Electrolytic capacitor 1. Turn OFF the power supply breaker.(For raising pressure, smoothing) 2. Discharge all three capacit

Page 77

– 78 –FILE NO. SVM-7008If the resistance value between1 (Red lead) − 2 (White lead)2 (White lead) − 3 (Black lead)3 (Black lead) − 1 (Re

Page 78

– 7 –Table 3-2-1 Thicknesses of annealed copper pipesNominal diameter1/43/81/25/8Outer diameter (mm)6.359.5212.7015.88Thickness (mm)R410A R220.80 0.8

Page 79

− 79 −How to remove the front panel1) Stop the operation of the air conditioner andturn off its main power supply.2) Pull the air inlet grille towar

Page 80 - 12. PART REPLACEMENT

− 80 −1) Remove the front panel, electrical part andthe horizontal louver following procedure 3.2) Remove the pipe holder at the rear side ofmain uni

Page 81

FILE NO. SVM-07008– 81 –1) Turn the power supply off to stop the operationof air conditioner.2) Remove the front panel.• Remove the 4 fixing screws.3)

Page 82

FILE NO. SVM-07008– 82 –<P.C. board layout> Solder side

Page 83 - <P.C. board layout>

FILE NO. SVM-07008– 83 –12-3-1. Outdoor Unit No. Part name Procedures Remarks1. Detachment1) Stop operation of the air conditioner, andturn off the ma

Page 84

FILE NO. SVM-07008– 84 –No. Part name Procedures Remarks1) Perform work of item 1 of 1.2) Remove screw (ST1T∅4 x 10s 1 pc.) ofthe upper part of the fr

Page 85

FILE NO. SVM-07008– 85 –No. Part name Procedures Remarks1) Disconnect lead wires and connectorsconnected from the control boardassembly to other parts

Page 86 - CN300 CN701

FILE NO. SVM-07008– 86 –No. Part name Procedures Remarks1) Perform work of item 1 of 1 and 1 of 2.2) Remove the flange nut fixing the fan motorand the

Page 87

FILE NO. SVM-07008– 87 –No. Part name Procedures Remarks1. Detachment1) Perform work of item 1 of 1 and 1 of 2.Requirement:Perform the work on a corru

Page 88

FILE NO. SVM-07008– 88 –No. Part name Procedures Remarks1)Cut the sensor 100 mm longer than oldone.2) Cut the protective tube after pulling out it(200

Page 89

– 8 –AØDd) Flare ProcessingMake certain that a clamp bar and copperpipe have been cleaned.By means of the clamp bar, perform the flareprocessing corre

Page 90 - Description Description

FILE NO. SVM 07008− 89 −13. EXPLODED VIEWS AND PARTS LIST13-1. Indoor Unit (E-Parts Assy)401405410411404403Location Part Location PartNo. No. No. No.4

Page 91

FILE NO. SVM-07008− 90 −13-2. Indoor Unit Location Part Location PartNo. No. No. No.201 43T00478 FRONT PANEL ASSY 213 43T19333 FIX-PIPE-SENSOR202 43

Page 92

FILE NO. SVM-07008− 91 −13-3. Outdoor UnitLocation Part Location PartNo. No.1 43T19335 FAN GUARD 15 43T49327 CUSHION,RUBBER2 43T20324 PROPELLER FAN

Page 93

FILE NO. SVM-07008− 92 −13-4. Outdoor Unit (E-Parts Assy)707704705703706702701708Location Part Location PartNo. No.701 43T62320 HEATSINK 705 43T60377

Page 94 - TOSHIBA CARRIER CORPORATION

FILE NO. SVM-03008– 87 –TOSHIBA CARRIER CORPORATION